DIN rail installation, for 2000V DC power system, high discharge capacity due to Metal Oxide Varistor (MOV)
| Model No. | SLP-PV2000/S |
|---|---|
| SPD according to IEC/EN 61643-31 | Type 2 / Class II / Class C |
| Maximum continuous operating DC voltage (DC+)-PE, (DC-)-PE Ucpv | 2000 V |
| Maximum continuous operating DC voltage (DC+)-(DC-) Ucpv | 2000 V |
| Nominal discharge current (8/20 μs) In | 20kA |
| Total discharge current (8/20 μs) Itotal | 40kA |
| Maximum discharge current (8/20 μs) Imax | 40kA |
| Voltage protection level (DC+)-PE, (DC-)-PE Up | 6.5 kV |
| Voltage protection level (DC+)-(DC-) Up | 6.5 kV |
| Residual Current at Uc IPE | < 0.5 mA |
| Response Time tA | < 25 ns |
| Short-Circuit Current Rating ISCPV | 1 kA |
| Number of Ports | 1 |