Type 1 Spark Gap Surge Protection Device FLP50GR-275/3S+1

Main Features:

  • Location of Use: Main Distribution Boards

  • Network Systems: TN-S, TT

  • Mode of Protection: L-N, N-PE

  • Surge Ratings: Iimp = 50 kA (10/350 μs), In = 50 kA (8/20 μs)

  • IEC/EN Category: Class l+II / Type 1+2

  • Protective Elements: Spark Gap

  • Housing: Monobloc Design

  • Compliance: IEC 61643-11:2011, EN 61643-11:2012
  • Main Specification

    Type 1 Spark Gap Surge Protection FLP50GR-275/3S+1 offers 50kA (10/350μs) & 100kA (8/20μs) surge ratings for three-phase systems (L1, L2, L3, PE terminals). Compliant with IEC 61643-11:2011 & EN 61643-11:2012 standards, it operates in -40°C to +70°C and handles 95% humidity.
    Model No.FLP50GR-275/3S+1
    Nominal AC Voltage (50/60 Hz) Uo / Un230V
    Maximum Continuous Operating Voltage (L-N) UC / (N-PE) UC275V
    Nominal Discharge Current (8/20 μs) (L-N) / (N-PE) In50 kA / 100 kA
    Maximum Discharge Current (8/20 μs) (L-N) / (N-PE) Imax100 kA
    Impulse Discharge Current (10/350 μs) (L-N) / (N-PE) Iimp50 kA / 100 kA
    Specific Energy (L-N) / (N-PE) W/R156.5 kJ/Ω / 2.5 MJ/Ω
    Voltage Protection Level (L-N) / (N-PE) Up1.8 kV / 1.5 kV
    Follow Current Interrupt Rating (N-PE) Ifi50 ARMS / 100 ARMS
    Max. Backup Fuse500 A gL / gG
    Short-Circuit Current Rating (AC) (L-N) ISCCR10 kA
    TOV Withstand 5 s (L-N) UT335 V
    TOV 120 min (L-N) UT530 V
    TOV Withstand 200 ms (N-PE) UT1200 V
    Number of Ports1

    Basic Circuit Diagram

    Type 1 Spark Gap Surge Protection FLP50GR-275/3S+1 is designed for three-phase TN-S/TT systems (3+1 configuration), providing L-N and N-PE protection. It features a built-in spark gap, remote signaling contacts, and complies with IEC 61643-11.

    Dimensions

    Type 1 Spark Gap Surge Protection FLP50GR-275/3S+1 has a compact monobloc design. The unit’s dimensions are 144 mm wide, 65 mm deep, and 95.5 mm high. It mounts on a 35 mm DIN rail in compliance with EN 60715.

    Installation Instructions

    Mount FLP50GR-275/3S+1 Type 1 Spark Gap Surge Protection near protected equipment. Connect line (L), neutral (N) & PE terminals securely. Ensure upstream overcurrent protection. Disconnect power before installation. Follow local codes. Only qualified personnel.

    Wiring Diagram & Installation

    The Spark Gap Surge Protection Device is DIN rail mountable. For TN-S/TT systems, use standard parallel wiring with connection leads <50cm for optimal lightning current discharge.

    Remote Signaling Terminal

    The integrated Remote Signaling Terminal provides real-time status monitoring for the Spark Gap Surge Protection Device. NO/NC contacts are available for remote alarming and centralized control.

    Documentation

    The Type 1 Spark Gap Surge Protection FLP50GR-275/3S+1 is certified per IEC/EN 61643-11. Comprehensive documentation includes detailed installation manual, technical datasheet, and declaration of conformity for project compliance.