Type 1 Spark Gap Surge Protection Device FLP50GR-275/3S

Main Features:

  • Location of Use: Main Distribution Boards

  • Network Systems: TN-C

  • Mode of Protection: L-PEN

  • Surge Ratings: Iimp = 50 kA (10/350 μs), In = 50 kA (8/20 μs)

  • IEC/EN Category: Class l+II / Type 1+2

  • Protective Elements: Spark Gap

  • Housing: Monobloc Design

  • Compliance: IEC 61643-11:2011, EN 61643-11:2012
  • Main Specification

    Type 1 Spark Gap Surge Protection Device FLP50GR-275/3S offers Iimp 50kA (10/350µs), Uc 275V, Up 1.8kV. Designed for TN-C systems (3+0 mode), with 500A backup fuse and remote signaling. Certified to IEC 61643-11.
    Model No.FLP50GR-275/3S
    Nominal AC Voltage (50/60 Hz) Uo / Un230V
    Maximum Continuous Operating Voltage (AC) UC275V
    Nominal Discharge Current (8/20 μs) In50 kA
    Maximum Discharge Current (8/20 μs) Imax100 kA
    Impulse Discharge Current (10/350 μs) Iimp50 kA
    Specific Energy W/R156.5 kJ/Ω
    Voltage Protection Level Up1800 V
    Max. Backup Fuse500 A gL / gG
    Short-Circuit Current Rating (AC) ISCCR10 kA
    TOV Withstand 5 s UT335 V
    TOV 120 min UT530 V
    Number of Ports1

    Basic Circuit Diagram

    Type 1 Spark Gap Surge Protection Device FLP50GR-275/3S is designed for TN-C systems (3+0 configuration), providing robust L-PEN protection with a built-in spark gap. It includes remote signaling contacts for status monitoring.

    Dimensions

    Type 1 Spark Gap Surge Protection Device FLP50GR-275/3S features compact dimensions of 90mm x 95.5mm x 144mm for 35mm DIN rail mounting, enabling space-efficient integration in distribution boards.

    Installation Instructions

    Type 1 Spark Gap Surge Protection Device FLP50GR-275/3S mounts on 35mm DIN rail. Torque terminals to 3.5-4.0 Nm. Use 6-35mm² (L/PEN) copper conductors. Connect remote contacts (11-12-14) for status monitoring.

    Wiring Diagram & Installation

    This Spark Gap Surge Protection Device is DIN rail mountable. Use standard parallel wiring , with connection leads <50cm for optimal lightning current discharge performance.

    Remote Signaling Terminal

    Remote Signaling Terminal monitors Spark Gap Surge Protection Device status. NO/NC contacts for remote control.

    Documentation

    Type 1 Spark Gap Surge Protection Device FLP50GR-275/3S is certified per IEC/EN 61643-11. Complete documentation includes installation manual, technical datasheet, and CE Declaration of Conformity.