Type 1 Spark Gap Surge Protection Device FLP50GR-275/2S features Iimp 50kA (10/350µs), Uc 275V, Up 1.8kV. Designed for TN-S systems (single-phase L-N+PE mode) with 500A backup fuse and remote signaling. IEC 61643-11 certified.
| Model No. | FLP50GR-275/2S |
|---|---|
| Nominal AC Voltage (50/60 Hz) Uo / Un | 230V |
| Maximum Continuous Operating Voltage (AC) UC | 275V |
| Nominal Discharge Current (8/20 μs) In | 50 kA |
| Maximum Discharge Current (8/20 μs) Imax | 100 kA |
| Impulse Discharge Current (10/350 μs) Iimp | 50 kA |
| Specific Energy W/R | 156.5 kJ/Ω |
| Voltage Protection Level Up | 1800 V |
| Max. Backup Fuse | 500 A gL / gG |
| Short-Circuit Current Rating (AC) ISCCR | 10 kA |
| TOV Withstand 5 s UT | 335 V |
| TOV 120 min UT | 530 V |
| Number of Ports | 1 |
Install the Type 1 Spark Gap Surge Protection Device FLP50GR-275/2S on a 35 mm DIN rail (clip-on type). Ensure proper connection to the main earthing bar. The minimum conductor cross-section for live/neutral wires is 6-35 mm², and for the earth wire is 16-35 mm². Tighten terminals with a torque of 3.5-4.0 Nm.