Type 1+2+3 Surge Protection FLP12,5VG-275/3S+1

Main Features:

  • Location of Use: Main Distribution Boards

  • Network Systems: TT, TN-S

  • Mode of Protection: L-N, N-PE

  • Surge Ratings: Iimp = 12.5 kA / 50 kA (10/350 μs), In = 20 kA (8/20 μs), Uoc = 6 kV (1.2/50 μs)

  • IEC/EN Category: Class l+II+III / Type 1+2+3

  • Protective Elements: High Energy MOV and GDT

  • Housing: Pluggable Design

  • Compliance: IEC 61643-11:2011, EN 61643-11:2012
  • Main Specification

    FLP12,5VG-275/3S+1 Surge Protection: 275V Uc, 20kA In, 12.5kA Iimp, 1.5kV Up. 3+1 circuit, pluggable with remote signal for main distribution boards.

    Model No.FLP12,5VG-275/3S+1
    Nominal AC Voltage (50/60 Hz) Uo / Un230V
    Maximum Continuous Operating Voltage (L-N) UC / (N-PE) UC275V
    Nominal Discharge Current (8/20 μs) (L-N) / (N-PE) In20 kA / 50 kA
    Maximum Discharge Current (8/20 μs) (L-N) / (N-PE) Imax50 kA / 100 kA
    Impulse Discharge Current (10/350 μs) (L-N) / (N-PE) Iimp12.5 kA / 50 kA
    Open Circuit Voltage (1.2/50 μs) Uoc 6 kV
    Total Discharge Current (8/20 μs) Itotal100 kA
    Total Discharge Current (10/350 μs) Itotal50 kA
    Specific Energy (L-N) / (N-PE) W/R40 kJ/Ω / 625 kJ/Ω
    Charge (L-N) / (N-PE) Q6.25 As / 25 As
    Voltage Protection Level (L-N) / (N-PE) Up1.5 kV / 1.5 kV
    Follow Current Ifnone
    Residual Current at Uc IPEnone
    Response Time (L-N) / (N-PE) tA< 25 ns / < 100 ns
    Max. Backup Fuse160 A gL / gG
    Short-Circuit Current Rating (AC) ISCCR50 kA
    TOV Withstand 5 s (L-N) UT335 V
    TOV 120 min (L-N) UT440 V
    TOV Withstand 200 ms (N-PE) UT1200 V
    Number of Ports1

    Basic Circuit Diagram

    Basic circuit: 3+1 Surge Protection (L1,L2,L3-N & N-PE). Provides coordinated L-N and N-PE protection in standard TN-S/TT systems with remote contacts.

    Dimensions

    This 3+1 Surge Protection unit features 72mm width, 89.6mm depth, and 99.6mm height. Compact DIN-rail design ensures easy panel integration.

    Installation Instructions

    Install this Surge Protection on 35mm DIN rail. Keep total wiring length (a+b+c) under 50cm. Use 160A max gG/gL backup fuse for safe three-phase system operation.